The precision, sensitivity and long service life of the mixing valve will be ensured only insofar as it is properly maintained and if it is correctly chosen beforehand.

In order to define the size of the mixing valve which is best adapted to a given installation, it is absolutely necessary to know two elements : the total instantaneous flow rate, and the dynamic pressure available to the flow for the hot and cold water, at the mixing valve's inlets.

It can be measured or calculated, by using the DARIES Chart or the WATTS software package, which is designed to validate the calculation carried out manually in order to choose the right mixing valve (according to pressures, pipe diameters, desired flow rate and number of points of use).
In no case should you permit static pressure greater than 10 bars.

The proper dimensioning of the mixing valve, that is, the choice of flow rate (according to the data in our technical leaflets).

The hot water temperature which must not exceed 85°C in order to avoid premature aging of the equipment and the installation, but must remain higher than the set point with a difference of 5°C between the two fluids.

The meter for the main water supply, whose given maximum flow rate determines the installation’s possible flow rate.

The length and diameter of the piping which, through pressure losses and water speed, will facilitate or complicate the installation’s operation.

For this reason, the diameter of the inlet pipes (Hot and Cold) and the outlet pipe diameter for mixed water departure, must be the same nominal diameter (DN) as the mixing valve, a difference of one diameter DN (in more or less) is only tolerated.



Connections :
All our mixers for Group Installations (T9107, T9715, ULTRAMIX and Flanged models) are designed to take in HOT water on the LEFT-hand side and COLD water on the RIGHT-hand side.

On special request, when this arrangement is impossible, mixers can be fitted out in the opposite manner with a specific cartridge type “IN”.